Kohler — Connection Procedure (Field Connections)

Installation · Field-connection terminal block

From a Kohler service manual covering: 12RES, 12RESL/12RESM1, 18RES. Check it applies to your exact model before use.

Applies to: Kohler 12RES, Kohler 18RES

Before you start

  • Hazardous voltage. Backfeed to the utility system can cause property damage, severe injury, or death. Install an automatic transfer switch.
  • Grounding electrical equipment. Hazardous voltage can cause severe injury or death.

Procedure

  1. 12RESL: Remove the cover from the electrical connection access area.
  2. Drill holes for conduit fittings as described for each model; use separate conduit for AC wiring and low-voltage engine start leads.
  3. Connect the leads from the transfer switch emergency source lugs to the L1 and L2 connections on the generator set terminal block.
  4. Connect the neutral (L0) and ground (GRD) leads from the ATS and the main panel to the corresponding connection points.
  5. Connect 120 VAC utility power to the terminals marked Utility Power (must be backed-up by the generator set).
  6. Connect the engine start leads from the automatic transfer switch or remote start switch to terminals 3 and 4 on the terminal block.
  7. 12RESL/12RESM1: Replace the cover over the electrical connection access area.

Specs & values

  • Engine start leads land on terminals 3 and 4
  • Load leads land on L1 and L2
  • Neutral L0, ground GRD

Full service-parts list: Kohler 12RES →, Kohler 18RES →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.