Kohler — Bus Bar Load Connection

Installation · Power connections

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Connect source/load phases as marked to prevent short circuits

Procedure

  1. Strip cable insulation carefully avoiding nicking conductors
  2. Clean cables with a wire brush to remove surface oxides
  3. Apply joint compound to aluminum conductor connections
  4. Follow phase markings A, B, C, N; single-phase connects to A and C
  5. Use compression washer, flat washer, and minimum grade 5 bolt for bus bar connections
  6. Tighten to torque values in Figure 27
  7. Tighten utility source cables to torque values shown on the circuit breaker
  8. Tighten emergency source and load cable lugs to torque values on the transfer switch label
  9. Wipe off excess joint compound after tightening

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • See Figure 27 Tightening Torque for Bus Bars

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.