Home›Repair guides›Kohler›Battery Electrolyte and Specific Gravity Check

Kohler — Battery Electrolyte and Specific Gravity Check

Maintenance

From a Kohler service manual covering: 7CCFKM, 7CCFKM / 7CCFKMR, 7CCKM, 7CCKM / 7CCKMR. Check it applies to your exact model before use.

Applies to: Kohler 7CCFKM, Kohler 7CCKM, Kohler K-582 engine

Before you start

  • Sulfuric acid in batteries can cause severe injury or death

Procedure

  1. Remove filler caps and check electrolyte up to bottoms of filler holes.
  2. Refill with distilled water or clean tap water; do not add fresh electrolyte.
  3. Use battery hydrometer to check specific gravity of each cell.
  4. Adjust gravity reading for electrolyte temperature.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Fully charged 1.260 at 80°F (26.7°C)
  • Charge if below 1.215 at 80°F
  • Cell difference not to exceed +/-0.01

Full service-parts list: Kohler 7CCFKM →, Kohler 7CCKM →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.