Home›Repair guides›Kohler›Arc Chute Replacement Procedure

Kohler — Arc Chute Replacement Procedure

Repair & overhaul

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Rubber insulating gloves class 0, safety glasses, and electrical hazard safety shoes required.

Procedure

  1. Prevent all connected generator sets from starting and disconnect power to the transfer switch.
  2. Open the enclosure and verify zero volts across each phase.
  3. Remove the arc chute hold down screws.
  4. Remove the arc chute and inspect the movable contact for damage.
  5. Install the new arc chute and holding screws and washers; torque to 2.8 Nm (25 in. lb.).
  6. Manually operate the switch several times to ensure that it does not stick.
  7. Close the enclosure, reconnect power, and enable the generator set.
  8. Test using the Automatic Operation Test Procedure.

Tools required

  • Basic electricians hand tools

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Arc chute screws 2.8 Nm (25 in. lb.)

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.