Kohler 48RCLB / 60RCLA — Voltage Calibration using the RDC2 Controller Keypad and Menus
Adjustments
For the Kohler 48RCLB / 60RCLA, from the Kohler service manual.
Applies to: Kohler 48RCLB, Kohler 60RCLA, Kohler KG6208 engine
Before you start
- Testing live electrical circuits. Hazardous voltage or current will cause severe injury or death.
Procedure
- With generator off, connect a digital multimeter to measure output voltage across L1 and L2 (AC volts).
- Start the generator set by pressing RUN.
- Navigate to the Generator Metering menu.
- Display Volts L1-L2 and compare with the voltmeter reading.
- Press Select; the voltage flashes. Adjust with up/down arrows to match the voltmeter.
- Press Select to save; wait 30 to 60 seconds for the reading to stabilize.
- For three-phase models, repeat for L2-L3 and L3-L1.
- Step down to Return and press Select to exit.
- Press OFF to stop the generator set.