Home›Repair guides›Kohler›Setting the OnCue Plus Password

Kohler 48RCLB / 60RCLA — Setting the OnCue Plus Password

Operation · RDC2 controller

For the Kohler 48RCLB / 60RCLA, from the Kohler service manual.

Applies to: Kohler 48RCLB, Kohler 60RCLA, Kohler KG6208 engine

Procedure

  1. Press Select and navigate to the networking Information menu.
  2. Press Select; Networking Status is displayed.
  3. Press the Down arrow; Networking Configuration is displayed.
  4. Press Select; Reset OnCue Password is displayed.
  5. Press and HOLD Select until Reset OnCue Password? No appears (No flashes).
  6. Press the Up arrow to change No to Yes.
  7. Press Select to reset the password; serial number and new password display for 10 seconds.
  8. Write down the new password for entry into the OnCue Plus program.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Kohler 48RCLB →, Kohler 60RCLA →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.