Kohler 48RCLB / 60RCLA — Procedure to Reset the Controller after a Fault Shutdown
Testing & diagnosis · RDC2 controller
For the Kohler 48RCLB / 60RCLA, from the Kohler operator's manual.
Applies to: Kohler 48RCLB, Kohler 60RCLA
Before you start
- Always identify and correct the cause of a fault shutdown before resetting the controller.
Procedure
- Press the Select button to go to the Overview menu.
- Press Select again; the active fault is displayed.
- Press Select; Confirm Clear Fault: NO is displayed.
- Press the Up arrow button; Confirm Clear Fault: YES is displayed.
- Press the Select button to enter YES and clear the fault.
- Press the Select button to return to the overview menu.
- Press AUTO to put the generator set into automatic mode.
Full service-parts list: Kohler 48RCLB →, Kohler 60RCLA →
Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.