Home›Repair guides›Kohler›Procedure to Change the Exercise Setting

Kohler 48RCLB / 60RCLA — Procedure to Change the Exercise Setting

Operation · RDC2 controller exerciser

For the Kohler 48RCLB / 60RCLA, from the Kohler operator's manual.

Applies to: Kohler 48RCLB, Kohler 60RCLA

Before you start

  • Use caution when navigating the controller menus; changing settings to incorrect values can adversely affect generator set operation or render the unit inoperable.

Procedure

  1. Press the AUTO button on the controller.
  2. Press the Select button to go to the main menu.
  3. Press the down arrow button to step to the Genset System menu.
  4. Press the Select button to enter the Genset System menu.
  5. Use the down arrow button to step to the next Exercise menu and press Select.
  6. Press the UP or Down arrow buttons to change the setting.
  7. Press the Select button to save the setting and move to the next.
  8. Repeat steps 5 through 8 to change the next item until the desired settings are displayed.
  9. Press Select to save after all settings have been selected; settings will stop flashing.
  10. If connected to a Model RXT transfer switch, set the Exercise Mode to loaded full speed, unloaded full speed, or unloaded cycle.
  11. Set the exercise frequency (weekly or every two weeks); weekly exercises are recommended.
  12. Press the down arrow button to step to the Return menu and press Select to return to the main menu.
  13. Check that the AUTO LED is lit.

Specs & values

  • Exercise time 20 minutes
  • Exercise frequency weekly or every other week

Full service-parts list: Kohler 48RCLB →, Kohler 60RCLA →

Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.