Home›Repair guides›Kohler›LED Optic Board Test Procedure

Kohler 48RCLB / 60RCLA — LED Optic Board Test Procedure

Testing & diagnosis · Alternator LED optic board / FRX activator board

For the Kohler 48RCLB / 60RCLA, from the Kohler service manual.

Applies to: Kohler 48RCLB, Kohler 60RCLA, Kohler KG6208 engine

Before you start

  • Testing the photo transistor circuit board. Hazardous voltage will cause severe injury or death. Do not expose the photo transistor board to external light.
  • Disconnecting the electrical load. Hazardous voltage will cause severe injury or death.

Procedure

  1. Remove the enclosure rear panel from the generator end.
  2. Remove the LED optic board and holder.
  3. With the generator running at no load, shine a flashlight at the exposed photo transistor.
  4. Observe AC output voltage; high output indicates the FRX activator board is functioning, and voltage should drop when the flashlight is removed.
  5. If high voltage exists with the flashlight off, stop the unit and tape over the photo transistor; restart to check for external light.
  6. With the generator running at no load, approximately 1--2 volts DC should be observed at 3B (+) and 5B (--) at the LED optic board.
  7. Shine the flashlight; the DC voltage reading should drop.
  8. Stop the generator set.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Approximately 1--2 volts DC at 3B (+) and 5B (--) at the LED optic board

Full service-parts list: Kohler 48RCLB →, Kohler 60RCLA →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Kohler repair guides →