Home›Repair guides›Kohler›Separate Excitation of Generator

Kohler 4.5 CKM — Separate Excitation of Generator

Testing & diagnosis · Generator rotor/stator

For the Kohler 4.5 CKM, from the Kohler service manual.

Applies to: Kohler 4.5 CKM, Kohler KT17II engine

Before you start

  • Battery gases can cause an explosion. Do not smoke or permit flame or spark near battery.

Procedure

  1. Disconnect all leads from voltage regulator.
  2. Connect an ammeter and a 12-Volt automotive battery to the positive (+) and negative (-) brush leads.
  3. Ammeter reading should approximate battery voltage divided by specified rotor resistance.
  4. Start engine and check that ammeter remains stable; increasing reading indicates shorted rotor.
  5. Check for AC output across stator leads and compare to Table 6-2.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 12 Volts / 4.6 Ohms = 2.6 Amps (rotor current)

Full service-parts list: Kohler 4.5 CKM →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.