Kohler 12RES — Voltage Adjustment Procedure

Adjustments · ADC controller

For the Kohler 12RES, from the Kohler service manual.

Applies to: Kohler 12RES

Procedure

  1. Connect a digital multimeter to the output leads or an electrical outlet on the load side, set to AC voltage.
  2. Start the generator set by moving the master switch to the RUN position.
  3. Use the ADC controller to adjust the voltage (parameter 1P) until the output voltage reaches the desired value.
  4. Adjust the voltage stability (gain, parameter 2P) to minimize light flicker.
  5. Readjust the voltage, if necessary.
  6. Set the multimeter to measure frequency.
  7. Adjust the engine speed to the cut-in frequency by adjusting the engine governor speed (parameter 4P).
  8. Adjust the volts/Hz (parameter 3P) until the voltage level measured begins to drop.
  9. Reset the engine speed to the operating frequency (50 or 60 Hz) by adjusting the governor speed (parameter 4P).
  10. Readjust the voltage stability (gain, parameter 2P), if necessary.
  11. Readjust the voltage (parameter 1P), if necessary.
  12. Save settings.
  13. Stop the generator set.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 85-132 VAC: 5 VAC/step coarse, 0.5 VAC/step fine (parameter 1P)
  • 180-251 VAC: 7 VAC/step coarse, 0.7 VAC/step fine (parameter 1P)
  • Cut-in frequency: 57.5 Hz at 60 Hz, 47.5 Hz at 50 Hz

Full service-parts list: Kohler 12RES →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.