Kohler 12RES — Verify acceptable installation site conditions

Installation · Generator set siting

For the Kohler 12RES, from the Kohler service manual.

Applies to: Kohler 12RES

Before you start

  • Recommended distance from a structure is dependent on state and local codes.

Procedure

  1. Aim exhaust away from or parallel to structure.
  2. Do not direct exhaust at play areas, patios, or congregation areas.
  3. Keep nearest window, vent, or door at least 5 feet from exhaust end.
  4. Maintain proper offset from structure.
  5. Keep windows and doors on adjacent walls closed.
  6. Keep furnace and similar intakes at least 10 feet from exhaust end.
  7. Install weed barrier and 3 inch thick gravel base or concrete pad.
  8. Keep plants, shrubs, and combustibles out of clearance area (min 4 ft from exhaust end).
  9. Refer to owners manual for other installation constraints.
  10. Keep plants, shrubs, and combustibles at least 18 inches from air intake.

Specs & values

  • Combustible wall: 5 ft
  • Non-combustible wall: 18 in min, 3 ft recommended
  • NFPA 37 requires at least 5 ft from combustible material

Full service-parts list: Kohler 12RES →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.