Kohler 12RES — Resetting Controller After Fault Shutdown
Maintenance · DC 2200 controller
For the Kohler 12RES, from the Kohler operator's manual.
Applies to: Kohler 12RES, Kohler CH 740 engine
Before you start
- Always identify and correct the cause of a fault shutdown before resetting the controller.
Procedure
- Check fault code displayed on controller before resetting.
- Move generator set master switch to OFF/RESET.
- Disconnect generator set from load using line circuit breaker or ATS.
- Find and correct cause of fault shutdown.
- Test operate by moving master switch to RUN and verify unit starts and runs.
- Move master switch to OFF/RESET and verify the unit stops.
- Reconnect generator set to load using line circuit breaker or ATS.
- Move master switch to AUTO for remote start operation.