Kohler 12RES — Procedure to Convert from NG to LPG

Installation · Fuel system (original design)

For the Kohler 12RES, from the Kohler service manual.

Applies to: Kohler 12RES

Before you start

  • Explosive fuel vapors can cause severe injury or death.
  • Accidental starting can cause severe injury or death.

Procedure

  1. Place the generator set master switch in the OFF/RESET position.
  2. Disconnect the utility power to the generator.
  3. Disconnect the generator set engine starting battery, negative lead first.
  4. Turn off and disconnect the fuel supply.
  5. Remove the hose clamp and fuel hose from the hose fitting.
  6. Use a straight-blade screwdriver to remove the NG orifice from the hose fitting.
  7. Insert the LPG orifice into the hose fitting and tighten until snug.
  8. Slide the hose onto the hose fitting and secure it with the clamp.
  9. Disconnect ignition timing leads 65 and N5 for LPG.
  10. Connect and turn on the new fuel supply.
  11. Reconnect the engine starting battery leads, negative lead last.
  12. Reconnect the utility power to the generator.
  13. Start the generator set by moving the master switch to the RUN position.
  14. Check for leaks using a gas leak detector.
  15. Run the generator set and check the operation.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Kohler 12RES →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.