Kohler 12RES / 18RES — Storage Procedure
Maintenance · Generator set
For the Kohler 12RES / 18RES, from the Kohler operator's manual.
Applies to: Kohler 12RES, Kohler 18RES, Kohler CH 740 engine, Kohler CH 980 engine
Procedure
- Operate the generator set until it reaches operating temperature, or about 15 minutes.
- Stop the generator set and, while still warm, drain the engine lubrication oil from the crankcase.
- Refill the crankcase with oil and run the generator set a few minutes to distribute the clean oil, then stop.
- Start the generator set, shut off the gas supply, and run until the engine stops; place the master switch in OFF/RESET.
- Remove the spark plugs and pour one tablespoon of engine oil into each spark plug hole.
- Install the spark plugs and ground the leads; toggle the master switch to crank two or three revolutions.
- Clean the exterior surface and seal all engine openings with nonabsorbent adhesive tape.
- Mask all areas to be used for electrical contact and spread a light film of oil on unpainted metallic surfaces.
- Perform battery storage last: disconnect the battery, negative (--) lead first, and clean it.
- Place the battery in a warm, dry location and connect to a float/equalize charger or charge monthly with a trickle charger.
Specs & values
- Perform before removing from service for three months or longer
- Run the generator set monthly whenever possible
Full service-parts list: Kohler 12RES →, Kohler 18RES →
Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.