Kohler 12RES / 18RES — Starting Generator Set
Operation
For the Kohler 12RES / 18RES, from the Kohler operator's manual.
Applies to: Kohler 12RES, Kohler 18RES, Kohler CH 740 engine, Kohler CH 980 engine
Procedure
- Local starting: move the generator set master switch to the RUN position to immediately start the generator set.
- Auto (automatic) starting: move the master switch to AUTO to allow startup by an ATS or remote start/stop switch.
- Close a contact across engine start leads 3 and 4 to signal the controller to start the generator set.
- The controller attempts to start three times (15 seconds crank and 15 seconds off) before an overcrank fault.
Full service-parts list: Kohler 12RES →, Kohler 18RES →
Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.