Katolite — RDP-110 Lamp Test Procedure

A Katolite service procedure — check it applies to your exact model before use.

Browse Katolite generators & specs →

Procedure

  1. Press and release the pushbutton - sound and all LED's should turn on
  2. Release the pushbutton and the alarm and LED'S should turn off
  3. Apply the 10 hertz signal
  4. Press and release the Lamp Test pushbutton
  5. Each LED and the horn should annunciate in the following order before repeating: Switch Not in Auto, Low Coolant Level Alarm, High Coolant Temperature Alarm, Low Oil Pressure Alarm, Overcrank Alarm, Overspeed Alarm, Emergency Stop Activated Alarm, Factory selectable LED, Sender Failure Alarm, EPS Supplying Load, High Coolant Temperature Pre-alarm, Low Coolant Temperature Pre-alarm, Low oil Pressure Pre-alarm, Low Fuel Level Pre-alarm, Battery Overvoltage Pre-alarm, Weak Battery Pre-alarm

Specs & torque values

  • 10 hertz signal required

Source: manual:RDP-110_Manual.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.