Katolite — RDP-110 Testing Procedure
A Katolite service procedure — check it applies to your exact model before use.
Browse Katolite generators & specs →
Procedure
- Connect the RDP-110 test setup as shown in Figure 9.
- Apply 24 Vdc control power. The Display Panel On LED should light.
- Press and hold the Lamp Test pushbutton. All LEDs should light and the horn should sound.
- Release the Lamp Test pushbutton to reset the indicators and horn.
- Apply the 10 Hz signal.
- Press and release the Lamp Test pushbutton. Observe that the LEDs and horn annunciate in the eighteen-step sequence indicated in Figure 10. This sequence will repeat until the Alarm Silence pushbutton is operated.
- Press and release the Alarm Silence to end the annunciation sequence.
- Remove the 10 Hz signal and 24 Vdc control power.
- Repeat the test with 100/120 Vac control power applied instead of 24 Vdc control power.
Tools required
- Power supply, 24 Vdc
- Power source, 100/120 Vac, 50/60 Hz
- Fuse, 1 ampere (2)
- Signal generator, 10 Hz, square wave, 5 volts peak-to-peak
Source: manual:RDP-110 Annunciator Manual_Revision F.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.