Katolite 280 -- 430 Frame — Restoring Residual Magnetism - Field Flashing
For the Katolite 280 -- 430 Frame.
Browse Katolite generators & specs →
Before you start
- CAUTION: Failure to remove the exciter field leads from the automatic voltage regulator during flashing procedures may destroy the regulator
- Batteries may explode when exposed to an electric arc
Procedure
- Shutdown the generator set
- Remove the exciter field leads F+ and F- from the regulator
- Connect the F+ and F- leads to the battery's corresponding positive and negative terminals using an appropriate length of lead wire to separate the battery from the point of connection
- After 3 to 5 seconds, remove the F- lead - an inductive arc should result
- If no arc is drawn, repeat the procedure
- Reconnect the F+ and F- leads to the regulator
- Restart the generator and verify that terminal voltage is developed
- If terminal voltage does not develop, repeat the field flashing procedure or consult the troubleshooting section
Tools required
- 12 volt battery
- lead wire
Specs & torque values
- 3 to 5 seconds connection time
Source: manual:MARATHON Magnaplus Generator 280_430 Installation Manual 2004.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.