Katolite — Exciter Field Lead Connection for Flashing
A Katolite service procedure — check it applies to your exact model before use.
Browse Katolite generators & specs →
Before you start
- Failure to remove the exciter field leads from the automatic voltage regulator during flashing procedures may destroy the regulator
- Batteries may explode when exposed to electric arcing
Procedure
- Remove the exciter field leads from the automatic voltage regulator during flashing procedures.
- Connect the F+ and F- leads to the battery's corresponding positive and negative terminals.
- Use an appropriate length of lead wire to separate the battery from the point of connection.
Tools required
- Battery
Specs & torque values
- F+ and F- leads
- Lead wire
Source: manual:MagnaPlus_Manual diode part .pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.