Katolite — Exciter Field Lead Connection for Flashing

A Katolite service procedure — check it applies to your exact model before use.

Browse Katolite generators & specs →

Before you start

  • Failure to remove the exciter field leads from the automatic voltage regulator during flashing procedures may destroy the regulator
  • Batteries may explode when exposed to electric arcing

Procedure

  1. Remove the exciter field leads from the automatic voltage regulator during flashing procedures.
  2. Connect the F+ and F- leads to the battery's corresponding positive and negative terminals.
  3. Use an appropriate length of lead wire to separate the battery from the point of connection.

Tools required

  • Battery

Specs & torque values

  • F+ and F- leads
  • Lead wire

Source: manual:MagnaPlus_Manual diode part .pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.