Procedure

  1. Verify unit alignment, three feet air space on all four sides, oil level, fuel connections, AC and DC wiring, battery and charger.
  2. Set Mode switch to manual with circuit breaker on; turn the utility supply to the transfer switch off.
  3. Press the start button and hold until engine starts, approximately 3 seconds or for 10 second intervals.
  4. Check no load voltage 240-245 and frequency 60-61 Hz; adjust engine speed if necessary (9kW only).
  5. Turn utility and generator circuit breakers on; set Mode switch to Auto.
  6. Press and hold the Push to Test button until the generator acceptable light comes on and stays on.
  7. Check loaded volts and frequency at E1 and E2 (voltage not below 220 V, frequency 60 Hz).

Tools required

  • AC volt and frequency meter Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • No load voltage 240-245
  • No load frequency 60-61 Amazon eBay Hz
  • Loaded voltage not below 220 V
  • Frequency at 60 Hz

Source: Katolight service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.