Katolight — Pre-Start Inspection

Operation · Generator

From a Katolight service manual covering: 280 -- 430 Frame, 280 frame, 360 frame, 430 frame. Check it applies to your exact model before use.

Browse Katolight generators & specs →

Before you start

  • MagnaPLUS generators may have voltage present at the lead terminals when the shaft is rotating. Do not permit operation until all leads have been connected and insulated.
  • Never bar over the engine generator set using the generator's fan.

Procedure

  1. Visually inspect for loose parts, bad connections, or foreign materials.
  2. Bar the set over by hand at least 2 revolutions to be sure it turns freely.
  3. Check all wiring against proper connection diagrams; ensure connections are tight and properly insulated.
  4. Verify that all equipment is properly grounded (earthed).
  5. Clear the surrounding area of materials that could be drawn into the generator.
  6. Check all fasteners for tightness.
  7. Check all access plates, covers, screens and guards; reinstall and secure if removed.
  8. Review all prime mover prestart-up instructions and ensure recommended steps were followed.
  9. Remove masking materials; verify nameplates and safety warning/caution decals are in place and visible.

Specs & values

  • Bar over by hand at least 2 revolutions

Source: Katolight service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.