Katolight E6921M1 / REO2IMI — Drying Wet Windings

Maintenance · Generator windings

For the Katolight E6921M1 / REO2IMI, from the Katolight service manual.

Browse Katolight generators & specs →

Procedure

  1. Open line switch or circuit breaker.
  2. Provide external source to blow warm, dry air through windings.
  3. Check generator system as Before Starting under Operation.
  4. Switch to Manual position if switch supplied.
  5. Disconnect and insulate terminal lug on F+ lead and CF+ lead if exciter has dual windings.
  6. Start engine and run for several hours.
  7. Shut down engine and check insulation resistance with 500 volt megohmmeter.
  8. Restore circuit after satisfactory insulation test.