Katolight E6921M1 / REO2IMI — Diode Test

Testing & diagnosis · Rotating rectifier diodes

For the Katolight E6921M1 / REO2IMI, from the Katolight service manual.

Browse Katolight generators & specs →

Procedure

  1. Disconnect all leads from one side of diode to be tested.
  2. With ohmmeter in lowest scale, measure across diode.
  3. Reverse ohmmeter leads and measure again.
  4. One reading should be very high; other should be approximately mid-scale.
  5. If both readings very high, diode is open.
  6. If both readings approximately mid-scale, diode is shorted.
  7. Replace any rectifier that gives doubtful results on either test.