Home Generators - Alpha Gen — Refer to the CE3X2 Telecom Series Enclosure Installation manual (p/n 031-099-C3)
For these Home Generators - Alpha Gen models: AlphaGen 3.5kW, AlphaGen 5.0kW, CE3X-2.
Browse Home Generators - Alpha Gen generators & specs →
Procedure
- 2.2.1 Ignition Battery Test Procedure
- 1.
- Connect a DVM (set for DC Volts) to the IGN BATT terminals. Connect
- the Red (+) lead of the DVM to the (+) terminal and the Black lead (-)
- of the DVM to the (-) terminal.
- 2.
- The DVM should indicate 12 VDC (+ 2 V , - 0 VDC). If this reading is
- lower than specified, recharge the batteries to 13.8 VDC before
- proceeding.
- WARNING:
- Do not use batteries (AGM or Gell Electrolyte)
- that read below 9.0 VDC, as the battery may be
- discharged below a safe point and could cause
- gassing during recharge.
- 2. Turn-Up and Test
- 28
- 031-099-B4-002 Rev. C
- TM
- ©2000
- 2.2.3 Starting a Local APU Test
- Procedure:
- 1.
- Locate APU control board (mounted alongside the ECM).
- 2.2.2 Engine Lubrication
- Check Engine lubrication Level Procedure:
- Check the engine crankcase oil level. If necessary, add oil to fill it to
- the FULL mark. DO NOT OVERFILL. Refer to the engine
- manufacturers’ operator’s manual for proper fill capacities and oil
- types. Ensure that the same brand of oil is used for topping the oil
- level, as some oil manufacturer’s additives are not compatible with
- each other. Never attempt to measure the oil level, or add oil, when
- the engine is in operation.
- CAUTION:
- Do not attempt to crank or start the engine
- before it has been serviced with the
- recommended oil, or engine failure will result.
- NOTE:
- Refer to the Alpha 5 Generator OPERATOR’S manual
- (p/n Tp-6076) provided by the manufacturer.
- 2.2
- Initial Operation, continued
- Generator Control Board
Source: manual:3.5kW 5.0kW Operation Maint. Manual.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.