Himoinsa — ECU Override

Operation · DSE 7310 control panel

From a Himoinsa service manual covering: HFW100T6, HFW130T6, HFW160T6, HFW180T6, HFW200T6, HFW230T6, HFW250T6, HFW300T6, HFW350T6, HFW60T6, HFW80T6, HFW90T6…. Check it applies to your exact model before use.

Browse Himoinsa generators & specs →

Before you start

  • ECU override is only applicable if the ECU is unpowered when in STOP mode.

Procedure

  1. Select STOP mode button (K) on the DSE controller.
  2. Press and hold the START button (F) to power the ECU; as controller is in STOP mode the engine will not start.
  3. Continue to hold the start button for as long as the ECU needs to be powered.
  4. The ECU will remain powered until a few seconds after the START button is released.

Source: Himoinsa service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.