Generac — Wn 600-2600 Amp: Switch Will Not Retransfer to Utility

Testing & diagnosis · Contactor Assembly (Wn 600-2600 Amp)

From a Generac service manual — check it applies to your exact model before use.

Browse Generac generators & specs →

Before you start

  • Disable generator from starting; disconnect negative battery cable.

Procedure

  1. Remove front cover.
  2. Remove top PCB cover.
  3. For testing, note PCB layout (see Figure 4).
  4. If switch not tripping to neutral, measure resistance between J1-6 and J1-8. Trip coil resistance should be measured, +/- 7%. If INFINITY, replace trip coil.
  5. With switch in generator position, measure resistance between BT1 and J2-6. 0.2 ohms. If INFINITY, replace BTS1 limit switch (071345).
  6. Measure resistance between BT2 and J2-5. 0.2 ohms. If INFINITY, replace BTS2 limit switch (071345).
  7. Measure resistance between J1-1 and J1-2. Closing coil resistance should be measured.
  8. If steps 4 and 5 good and switch not in neutral, push manual trip button to trip to neutral. Measure resistance between A2 and J2-2. 0.2 ohms. If INFINITY, replace LS (074672A).
  9. Measure resistance between A1 and J1-1. 0.2 ohms. If INFINITY, measure resistance across AX contacts of AXBX limit switch (071345).
  10. If AX contacts closed, measure resistance between NO/Com (upper/lower) contacts on LS (074672A). If INFINITY, replace.
  11. If all steps good, replace PCB (082428).