Generac — Wn 600-2600 Amp: Switch Will Not Retransfer to Utility
Testing & diagnosis · Contactor Assembly (Wn 600-2600 Amp)
From a Generac service manual — check it applies to your exact model before use.
Browse Generac generators & specs →
Before you start
- Disable generator from starting; disconnect negative battery cable.
Procedure
- Remove front cover.
- Remove top PCB cover.
- For testing, note PCB layout (see Figure 4).
- If switch not tripping to neutral, measure resistance between J1-6 and J1-8. Trip coil resistance should be measured, +/- 7%. If INFINITY, replace trip coil.
- With switch in generator position, measure resistance between BT1 and J2-6. 0.2 ohms. If INFINITY, replace BTS1 limit switch (071345).
- Measure resistance between BT2 and J2-5. 0.2 ohms. If INFINITY, replace BTS2 limit switch (071345).
- Measure resistance between J1-1 and J1-2. Closing coil resistance should be measured.
- If steps 4 and 5 good and switch not in neutral, push manual trip button to trip to neutral. Measure resistance between A2 and J2-2. 0.2 ohms. If INFINITY, replace LS (074672A).
- Measure resistance between A1 and J1-1. 0.2 ohms. If INFINITY, measure resistance across AX contacts of AXBX limit switch (071345).
- If AX contacts closed, measure resistance between NO/Com (upper/lower) contacts on LS (074672A). If INFINITY, replace.
- If all steps good, replace PCB (082428).
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- +/- 7%
- 0.2 ohms
- INFINITY
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.