Generac — Wn 100-400 Amp: Switch Will Not Retransfer to Utility
Testing & diagnosis · Contactor Assembly (Wn 100-400 Amp)
From a Generac service manual — check it applies to your exact model before use.
Browse Generac generators & specs →
Before you start
- Disable generator from starting; disconnect negative battery cable.
Procedure
- Remove front cover.
- For testing, note PCB layout (see Figure 2).
- If switch not tripping to neutral, measure resistance between J2-6 and J2-7. Trip coil resistance should be measured. If INFINITY, replace trip coil.
- Remove single Phillips head screw holding PCB. Unplug male to female connector. Verify contactor in utility position. On female side, measure ohms between Blue and Gray wires: 0.2 ohms. Measure ohms b
- If steps 3 & 4 good, switch should be tripping to neutral.
- If not in neutral, push manual trip button to trip to neutral.
- Measure resistance between A1 and J3-2. 0.2 ohms. If INFINITY, verify neutral position and test AXBX limit switch. If AXBX good, test select LS: place meter lead on upper front contact of AXBX and oth
- Measure resistance between A2 (J1-2) and J3-1. 0.2 ohms. Push down select coil button: open or INFINITY. If INFINITY, verify neutral and measure ohms between J1-2 and J3-4: 0.1 ohms. If open or INFINI
- If 0.1 ohms between J1-2 and J3-4, measure resistance between J3-4 and J3-1: 0.2 ohms. If open or INFINITY, replace select LS (074672A).
- If all tests satisfactory, replace PCB.
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- 0.2 ohms
- 0.1 ohms
- INFINITY
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.