Generac — W Style: Switch Will Not Transfer to Generator
Testing & diagnosis · Contactor Assembly (W)
From a Generac service manual — check it applies to your exact model before use.
Browse Generac generators & specs →
Before you start
- Disable generator from starting; disconnect negative battery cable; verify utility power secured.
Procedure
- Remove the cover on the contactor assembly.
- Set multimeter to ohms scale. Measure coil resistance and compare to chart.
- On J3 block, measure resistance between red wire (blue covering) and white wire (yellow covering).
- Measure resistance from red wire (blue covering) to white wire (blue covering)/red wire (yellow covering).
- Measure resistance from white wire (yellow covering) to white wire (blue covering)/red wire (yellow covering).
- If proper values not measured, replace closing coil. If proper, proceed.
- Remove screw from PCB and unplug harness. Manually transfer to utility position if needed.
- Measure resistance between yellow and brown wires on female side of plug. Less than 1 ohm. If not, replace LS1 (0D4516).
- Measure resistance between blue and brown wires. INFINITY. If not, replace LS1 (0D4516).
- Measure resistance between orange and gray wires. Less than 1 ohm. If not, replace LS2 (0D4516).
- Measure resistance between green and gray wires. INFINITY. If not, replace LS2 (0D4516).
- If all tests favorable, replace PCB (0D7400).
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- coil resistance per chart
- less than 1 ohm
- INFINITY
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.