Generac — Transfer Back to Utility Power Source (Manual)
Operation · Transfer Switch
From a Generac owner's manual — check it applies to your exact model before use.
Applies to: Generac 7 kW PowerPact
Procedure
- Set the Main Circuit Breaker (Generator Disconnect) to OFF (OPEN).
- Allow the engine to run for 2 minutes at no-load to stabilize internal temperatures.
- Press the Control Panel OFF button; the engine should shut down.
- Ensure utility power supply to the transfer switch is turned off.
- Use the manual transfer handle to move the main contacts back to their UTILITY position.
- Turn on the utility power supply to the transfer switch.
- Press the Control Panel AUTO button.
Full service-parts list: Generac 7 kW PowerPact →
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.