Home›Repair guides›Generac›Transfer Back to Utility Power Source (Manual)

Generac — Transfer Back to Utility Power Source (Manual)

Operation · Transfer Switch

From a Generac owner's manual — check it applies to your exact model before use.

Applies to: Generac 7 kW PowerPact

Procedure

  1. Set the Main Circuit Breaker (Generator Disconnect) to OFF (OPEN).
  2. Allow the engine to run for 2 minutes at no-load to stabilize internal temperatures.
  3. Press the Control Panel OFF button; the engine should shut down.
  4. Ensure utility power supply to the transfer switch is turned off.
  5. Use the manual transfer handle to move the main contacts back to their UTILITY position.
  6. Turn on the utility power supply to the transfer switch.
  7. Press the Control Panel AUTO button.

Full service-parts list: Generac 7 kW PowerPact →

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.