Before you start

  • Do not activate the transfer switch manually until all power voltage supplies are positively turned off

Procedure

  1. Set generator main circuit breaker to OFF (open).
  2. Let engine run one to two minutes at no-load.
  3. Set Auto/Off/Manual switch to OFF; engine should shut down.
  4. Check that utility power supply to transfer switch is turned OFF.
  5. Move manual transfer handle contacts back to Utility position.
  6. Turn ON utility power supply to the transfer switch.
  7. Set system to automatic operation.

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.