Generac — TO/OFF/MANUAL switch is set to OFF.
For these Generac models: 04916-0, Air-cooled 11 kW Generators.
Browse Generac generators & specs →
Procedure
- 2. Check the tag on the engine for oil viscosity and classification. Verify that the correct recommend- ed oil is used in the engine (see Section 4.3.1). If necessary, drain and refill with the proper oil.
- 3. Check the state of the battery. Fill all cells of unsealed batteries to the proper level with dis- tilled water. DO NOT USE TAP WATER IN THE BATTERY. Recharge the battery to 100 percent state of charge, or, if defective, replace the battery.
- 4. Clean and wipe the entire generator.
- 5. Remove the 7.5A and 15A fuses from the genera- tor control panel. Reconnect the battery. Observe battery polarity. Damage may occur if the battery is connected incorrectly.
- 6. Open the fuel shutoff valve.
- 7. Insert the 7.5A and 15A fuses into the generator control panel. Start the unit by moving the AUTO/ OFF/MANUAL switch to MANUAL. Allow the unit to warm up thoroughly.
- 8. Stop the unit by setting the AUTO/OFF/MANUAL switch to OFF.
- 9. Turn on the utility power to the transfer switch.
- 10. Set the AUTO/OFF/MANUAL switch to AUTO.
- 11. The generator is now ready for service.