Generac — TO/OFF/MANUAL switch is set to OFF.
For these Generac models: 04916-0, Air-cooled 11 kW Generators.
Browse Generac generators & specs →
Procedure
- 2. Check the tag on the engine for oil viscosity and classification. Verify that the correct recommend- ed oil is used in the engine (see Section 4.3.1). If necessary, drain and refill with the proper oil.
- 3. Check the state of the battery. Fill all cells of unsealed batteries to the proper level with dis- tilled water. DO NOT USE TAP WATER IN THE BATTERY. Recharge the battery to 100 percent state of charge, or, if defective, replace the battery. See “Specifications,” Section 1.6, for type and size.
- 4. Clean and wipe the entire generator.
- 5. Remove the 7.5A and 15A fuses from the genera- tor control panel. Reconnect the battery. Observe battery polarity. Damage may occur if the battery is connected incorrectly.
- 6. Open the fuel shutoff valve.
- 7. Insert the 7.5A and 15A fuses into the generator control panel. Start the unit by moving the AUTO/ OFF/MANUAL switch to MANUAL. Allow the unit to warm up thoroughly.
- 8. Stop the unit by setting the AUTO/OFF/MANUAL switch to OFF.
- 9. Turn on the utility power to the transfer switch.
- 10. Set the AUTO/OFF/MANUAL switch to AUTO.
- 11. The generator is now ready for service. NOTE: If the battery was dead or disconnected, the exer- cise timer must be reset. Section 4 — Maintenance Air-cooled 11 kW Generators