Generac — Testing The Smart A/C Module
Testing & diagnosis
From a Generac service manual covering: RTSC400A3, RTSW300A3, RTSW400A3. Check it applies to your exact model before use.
Browse Generac generators & specs →
Procedure
- Turn on the Utility supply to the ATS.
- Verify managed loads are powered and all LEDs illuminate on Smart A/C Module.
- Press the TEST button on the Smart A/C Module.
- Verify that all connected loads to be shed become disabled.
- After five (5) minutes verify A/C 1 is energized and Status LED A/C 1 is ON.
- After another 15 seconds, verify A/C 2 is energized and Status LED A/C 2 is ON.
- After another 15 seconds, verify Load A/C 3 is energized and Status LED Load A/C 3 is ON.
- After another 15 seconds, verify A/C 4 is energized and Status LED A/C 4 is ON.
Specs & values
- Recovery: A/C 1 at five (5) minutes
- Recovery: A/C 2 after 15 seconds
- Recovery: A/C 3 after 15 seconds
- Recovery: A/C 4 after 15 seconds
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.