Generac — Testing The SACM

Testing & diagnosis · Smart A/C Module (SACM)

From a Generac service manual covering: RTSC400A3, RTSW300A3, RTSW400A3. Check it applies to your exact model before use.

Browse Generac generators & specs →

Procedure

  1. Turn on the utility supply to the ATS.
  2. Verify managed loads are powered and all LEDs illuminate on SACM.
  3. Press the TEST button on the SACM.
  4. Verify that all of the connected loads to be shed become disabled.
  5. After five minutes, verify A/C 1 is energized and Status LED A/C 1 is ON.
  6. After another 15 seconds, verify A/C 2 is energized and Status LED A/C 2 is ON.
  7. After another 15 seconds, verify Load A/C 3 is energized and Status LED A/C 3 is ON.
  8. After another 15 seconds, verify A/C 4 is energized and Status LED A/C 4 is ON.