Generac — Testing The SACM
Testing & diagnosis · Smart A/C Module (SACM)
From a Generac service manual covering: RTSC400A3, RTSW300A3, RTSW400A3. Check it applies to your exact model before use.
Browse Generac generators & specs →
Procedure
- Turn on the utility supply to the ATS.
- Verify managed loads are powered and all LEDs illuminate on SACM.
- Press the TEST button on the SACM.
- Verify that all of the connected loads to be shed become disabled.
- After five minutes, verify A/C 1 is energized and Status LED A/C 1 is ON.
- After another 15 seconds, verify A/C 2 is energized and Status LED A/C 2 is ON.
- After another 15 seconds, verify Load A/C 3 is energized and Status LED A/C 3 is ON.
- After another 15 seconds, verify A/C 4 is energized and Status LED A/C 4 is ON.