Generac — Testing All Stator Windings to Ground

Testing & diagnosis

From a Generac service manual covering: GPS 12500, GPS 15000, GPS 17500. Check it applies to your exact model before use.

Applies to: Generac GPS 12500, Generac GPS 15000

Before you start

  • Disconnect electronic components, relays, Voltage Regulators before high voltage insulation testing

Procedure

  1. Disconnect stator output leads Wire 11 and Wire 44 from 50A circuit breaker.
  2. Remove stator output lead Wire 22 from neutral terminal on back of 50A outlet.
  3. Disconnect C1 connector from bottom of control panel (right side facing panel).
  4. Connect terminal ends of Wires 11, 22, and 44 together.
  5. Connect Hi-Pot red probe to joined leads; black lead to clean frame ground.
  6. Set tester to 1500 volts; apply voltage no longer than 1 second.
  7. If breakdown lamp lights, clean and dry stator then repeat test.
  8. If stator fails second test, replace stator assembly.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 1500 volts
  • Do not apply voltage longer than 1 second

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.