Generac — Test Stator Insulation Resistance

Testing & diagnosis

From a Generac service manual covering: 9202-1, 9203-1, 9204-1, 9205-1, 9206-1, 9207-1, 9290-2, 9509-2, 9592, 9593-0, 9593-1, 9593-2…. Check it applies to your exact model before use.

Applies to: Generac 9592

Before you start

  • Do not apply voltage longer than one second.
  • Do not connect tester leads to any leads routed into the generator control panel.

Procedure

  1. Disconnect and isolate all stator leads.
  2. Connect the terminal ends of all stator leads together.
  3. Connect tester leads across all stator leads and to frame ground on the stator can.
  4. Apply a voltage of 1500 volts; do not apply longer than one second.
  5. If breakdown indicated, clean, dry and re-test; replace stator if it fails the second test.
  6. Also test between isolated windings and between parallel windings at 1500 volts.

Tools required

  • megohmmeter or hi-pot tester Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Stator test voltage 1500 volts
  • Minimum insulation resistance = rated volts / 1000 + 1 megohms

Full service-parts list: Generac 9592 →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.