Generac — Test Stator Insulation - Air Cooled Units

Testing & diagnosis

From a Generac service manual — check it applies to your exact model before use.

Browse Generac generators & specs →

Procedure

  1. Disconnect stator AC output leads 11 and 44 from the main line circuit breaker.
  2. Remove the wire nut joining leads 22 and 33 and separate the leads.
  3. Disconnect stator excitation winding leads 2 and 6 and battery charge winding leads 55, 66, and 77.
  4. Connect the terminal ends of all stator leads together, isolated from ground.
  5. Connect the red Hi-Pot test probe to the joined leads and black probe to clean frame ground.
  6. Set tester to 500 volts and turn on for one second only, observing breakdown lamp.
  7. If breakdown lamp comes on, clean and dry the stator and repeat the test.
  8. If the stator fails the second test, replace the stator assembly.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 500 volts
  • Do not apply voltage longer than 1 second.

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.