Generac — Test Stator DPE Winding

Testing & diagnosis

From a Generac service manual — check it applies to your exact model before use.

Browse Generac generators & specs →

Procedure

  1. Disconnect Wire No. 2 from the excitation circuit breaker and Wire No. 6 from the voltage regulator.
  2. Set a VOM to Rx1 and zero the meter.
  3. Connect the VOM test leads across Wires No. 2 and 6. The VOM should read approximately 1.1 ohms.
  4. Set the VOM to a high resistance scale and zero the meter.
  5. Connect one test lead to Wire No. 2 and the other to clean frame ground. The meter should read infinity.
  6. Test Wire No. 2 to Wire No. 11 and Wire No. 44 for infinity.
  7. Disconnect Wire No. 66 from the battery charge rectifier and test Wire No. 2 to Wire No. 66 for infinity.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Approximately 1.1 ohms
  • Infinity for grounded/shorted condition

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.