Generac — Test Rotor Insulation

Testing & diagnosis

From a Generac service manual covering: 9202-1, 9203-1, 9204-1, 9205-1, 9206-1, 9207-1, 9290-2, 9509-2, 9592, 9593-0, 9593-1, 9593-2…. Check it applies to your exact model before use.

Applies to: Generac 9592

Before you start

  • Do not exceed 1000 volts and do not apply voltage longer than 1 second.

Procedure

  1. Disconnect wires from the rotor brushes or remove the brush holders with brushes.
  2. Connect the positive test lead to the positive slip ring (nearest the rotor bearing).
  3. Connect the negative test lead to a clean frame ground such as the rotor shaft.
  4. Apply 1000 volts; do not apply voltage longer than one second.
  5. If breakdown indicated, clean and dry the rotor then repeat; replace rotor if it fails the second test.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Rotor test voltage 1000 volts
  • Rotor minimum insulation resistance 1.5 megohms

Full service-parts list: Generac 9592 →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.