Generac — Starting the Unit
Operation · Engine
From a Generac owner's manual covering: MLT3060K, MLT3060M, MLT3080KV. Check it applies to your exact model before use.
Applies to: Generac MLT Light Tower, Generac MLT3060K, Generac MLT3060M, Mitsubishi L3E-W461ML engine
Before you start
- Equipment Damage. Never start engine with circuit breakers switched on.
- Do not continuously crank engine for more than ten seconds.
Procedure
- Verify main circuit breaker and individual light circuit breakers are OFF (O).
- Turn engine start switch to GLOW PLUG position and hold for five seconds or until glow plug indicator turns red. (Kubota units do not have glow plug indicator.)
- Turn key to START position and hold until engine cranks and starts.
- Release key; it will move to RUN position.
- Allow engine to reach normal operating temperature before switching on loads.
Specs & values
- Glow plug hold: 5 seconds
- If oil pressure not obtained within 15 seconds, low oil shutdown stops engine.
Full service-parts list: Generac MLT Light Tower →, Generac MLT3060K →, Generac MLT3060M →
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.