Generac — Shutting Generator Down While Under Load

Operation · Generator and transfer switch

From a Generac service manual covering: RTSC400A3, RTSW300A3, RTSW400A3. Check it applies to your exact model before use.

Browse Generac generators & specs →

Before you start

  • To avoid equipment damage, follow these steps, in order, when shutting the generator down during utility outages.

Procedure

  1. Turn the main utility disconnect off.
  2. Turn the generator MLCB (generator disconnect) to OFF (OPEN).
  3. Run the generator for approximately one minute for proper cooling.
  4. Turn the generator OFF.
  5. To turn back ON: put generator into AUTO, start and warm-up for a few minutes.
  6. Set the MLCB (generator disconnect) to ON (CLOSED).

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.