Home›Repair guides›Generac›Utility Voltage Checks

Generac RN100 — Utility Voltage Checks

Testing & diagnosis · power monitor relay

For the Generac RN100, from the Generac service manual.

Browse Generac generators & specs →

Before you start

  • Contact with live terminals causes fatal shock

Procedure

  1. Turn ON UTILITY power supply
  2. Check voltage across N1-N2, N2-N3, N1-N3
  3. Check voltage across N1-NEUTRAL, N2-NEUTRAL, N3-NEUTRAL
  4. Locate 3-phase power monitor relay
  5. Verify LED green and ON
  6. If LED not ON rotate potentiometer counter-clockwise
  7. When voltage correct turn OFF UTILITY supply

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 208V system: LED green ON
  • 480V system: LED NORM indicator ON
  • Factory dropout: 80% nominal (208V=166V, 480V=384V)

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.