Generac RN100 — Generator Voltage Checks

Testing & diagnosis · generator output

For the Generac RN100, from the Generac service manual.

Browse Generac generators & specs →

Before you start

  • Generator output voltage present; contact causes fatal shock

Procedure

  1. Set AUTO/OFF/MANUAL to MANUAL
  2. Generator cranks and starts
  3. Warm up at no-load for 5 minutes
  4. Set main circuit breaker ON
  5. Check no-load voltage with AC voltmeter
  6. Measure E1-E2, E2-E3, E1-E3
  7. Measure E1-NEUTRAL, E2-NEUTRAL, E3-NEUTRAL
  8. Verify frequency 60-62 Hz
  9. Verify phase rotation
  10. Turn OFF utility supply
  11. Set main circuit breaker OFF
  12. Set AUTO/OFF/MANUAL to OFF

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Frequency: 60-62 Hz
  • 208/480V phase-to-phase: 208-212V or 470-485V
  • 120/277V phase-to-neutral: 120-122V or 272-282V

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.