Generac — Remote Shutdown Switch Connections

Installation · Remote shutdown switch / STOP terminals

From a Generac service manual covering: PWRcell M3, PWRcell M3 DCB, PWRcell M4, PWRcell M4 DCB, PWRcell M5, PWRcell M5 DCB, PWRcell M6, PWRcell M6 DCB. Check it applies to your exact model before use.

Browse Generac generators & specs →

Before you start

  • If polarity is wired incorrectly, neither device will see a STOP condition.

Procedure

  1. Remove the 14 AWG jumper (A) installed on the STOP terminals before installing an external shutdown switch.
  2. Connect the wiring (B) to the external shutdown switch (field supplied) to battery STOP terminals.
  3. When the switch is in the OPEN or OFF position the remote shutdown will be activated; CLOSED or ON deactivates it.
  4. Test the remote shutdown switch operation after installation.

Specs & values

  • STOP Terminals accept 20 to 12 AWG, solid or stranded wire
  • Switch rated for STOP circuit voltage of 12 VDC minimum and current greater than or equal to 5 mA
  • 14 AWG THWN (600 V) wiring can be used

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.