Generac QUIETPACT 75 — Generator Conversion to 120 Volts Only, Dual Circuits

Installation · Electrical enclosure

For the Generac QUIETPACT 75, from the Generac owner's manual.

Applies to: Generac QuietPact 75

Before you start

  • Do not connect loads in excess of circuit breaker ratings.
  • Recommended to be performed by a Generac Authorized Service Dealer.

Procedure

  1. Disconnect battery power from the generator.
  2. Re-route stator lead 44 to ground stud previously occupied by lead 33.
  3. Move #18 AWG wire #44 from top of CB1A to top of CB1; renumber as #11.
  4. Re-route stator lead 33 to line side terminal on CB1 (renamed CB1A).
  5. Renumber ground wire 33 as wire 44.
  6. Renumber wire 44A as 33A.
  7. Connect a 12 AWG jumper between line breakers CB1 and CB1A.
  8. Remove the tie bar between the two line breaker switch handles.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Line breakers CB1 and CB1A trip rating 35 amps

Full service-parts list: Generac QuietPact 75 →

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.