Generac — Procedure
For these Generac models: 04916-0, Air-cooled 11 kW Generators.
Browse Generac generators & specs →
Procedure
- 3. Fuel Pressure incorrect.
- 3. Confirm fuel pressure to regulator is 5-7" water column (0.18 to 0.25) for natural gas; 10-12” water col- umn (0.36 to 0.43 psi) for liquid propane vapor. The AUTO/OFF/MANUAL switch
- 1. Defective switch.
- 1. * is set to OFF, but the engine
- 2. AUTO/OFF/MANUAL switch
- 2. * continues to run. wired incorrectly.
Source: manual:GeneracPowerSystems0049160UsersManual559844.1133830900.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.