Generac — Preparing Genset for Start-up

Installation · Generator set

From a Generac owner's manual covering: 4.6L 80kW, 5.4L 100kW, 6.8L 130kW, 6.8L 150kW, QT 6.8L 100kW. Check it applies to your exact model before use.

Applies to: Generac QT 6.8L 100kW, Generac V-type engine

Before you start

  • Before working on the generator, ensure the AUTO/OFF/MANUAL switch is in the OFF position and the 120VAC supply to the battery charger is switched OFF.

Procedure

  1. Ensure that the 120VAC circuit breaker to the battery charger is open.
  2. Remove the fuse from the control panel (15 Amp ATO fuse).
  3. Connect the battery cables to the battery; attach negative battery cable last.
  4. Close the 120VAC circuit breaker to the battery charger.
  5. Measure the voltage at the battery before and after the charger is turned on.
  6. Verify all AC electrical connections are tight at the circuit breaker and transfer switch.
  7. Check all hoses, clamps and fittings for leaks or damage.
  8. Open the valve to the engine fuel line and bleed the fuel system of air.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Fuel pressure must be as listed in the Specifications

Full service-parts list: Generac QT 6.8L 100kW →

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.