Generac — Overspeed Shutdown Adjustment

Adjustments · Engine Control Circuit Board

From a Generac service manual covering: IM100G, IM80G, NP100G, NP80G. Check it applies to your exact model before use.

Browse Generac generators & specs →

Procedure

  1. Turn the OVERSPEED SHUTDOWN POT counterclockwise until it just contacts its stop. DO NOT FORCE.
  2. Connect an accurate AC frequency meter across the generator AC output leads.
  3. Start the engine, let it stabilize and warm up at no-load.
  4. Slowly increase engine speed until the frequency meter reads 69-71 Hertz.
  5. Hold the throttle at 69-71 Hertz, then slowly turn the OVERSPEED SHUTDOWN POT clockwise. When the engine shuts down, overspeed setting is correct.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Shutdown at approximately 69-71 Hertz (2070-2130 rpm)

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.