Generac — Over Speed (Shutdown Alarm)
For these Generac models: EcoGen 6kW Generator, GT-530.
Applies to: Generac Ecogen 6Kw Generator, Generac Gt 530
Before you start
- Second Priority (Non-latching) Displayed on the control panel
Procedure
- 3000 RPM for three (3) seconds or 3300 RPM immediately. This
- 15 seconds, then re-crank the engine. If no RPM signal is detected
- 30 seconds it will shut down. The under-frequency setting is 55
- 15 seconds, it shuts down.
- 0.5 seconds, an alarm will be issued and the unit will shut down.
- 3.5.2
- 12.4 volts. Battery voltage is not monitored during the crank
- 3.5.3
Source: manual:696471058185_use.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.